Ordering Code : |
GNEXB2LD2DC024AB1 |
| Energy : |
5 Joules (5Ws) |
| Flash Rate : |
DC voltages: 1Hz (60fpm), 1.5Hz (90fpm) & double flash AC voltages: 1Hz (60fpm) |
| Alarm Stage : |
DC units - 2 , Double strike pattern can be remotely switched |
| Peak Candela : |
500,000 cd - calculated from energy (J) |
Source : |
Array of 4 x High Power Cree® LED's |
Modes : |
1Hz flash (60 fpm)
1.5Hz flash (90 fpm)
2Hz flash (120 fpm)
Double strike flash
Triple strike flash
High Power Steady
Low Power Steady |
| Effective Intensity (cd) : |
250 cd - calculated from energy (J) |
Peak Candela (cd): |
45,449 cd - measured ref to I.E.S
|
| Effective Intensity (cd) : |
117.93 cd - measured ref to I.E.S |
Lens Color : |
Amber, Blue, Clear, Green, Magenta, Red & Yellow |
| Supply Voltage(DC) : |
12Vdc; 24vdc; 48Vdc |
Supply Voltage(AC) : |
115V AC ; 220V AC |
Ingress Protection Rate : |
IP66 |
| Current Consumption : |
822mA @20-28VDC , 342mA @42-54VDC , 328mA @110-125VAC , 168mA @220-240VAC |
| Enclosure Material : |
UV stable GRP (glass reinforced polyester) |
| Color : |
Natural Red |
| Cable Entries : |
2 x M20 ISO (1 stopping plug inc.) Adaptors to M25, 1/2" & 3/4" NPT can be specified |
| Terminal : |
0.5 to 2.5mm² |
| Enclosure Volume : |
<2 litres |
| Line Monitor : |
Blocking diode included , EOL Min. 500 Ohm 2w , or 3k3 Ohm 0.5w resistor or diode (DC versions) can be fitted |
| Tube Life : |
Emissions are reduced to 70% after 5 million flashes |
| Operating Temperature : |
-50° to +70°C (-58°F to +158°F) |
| Relative Humidity : |
95% - Additional tropicalisation is recommended for applications where both high relative humidity and high ambient temperatures exist |
| Weight : |
1.5kg/3.3lbs |
| Coding : |
- II 2G Ex db IIC Gb T6 Ta -50°C to +40°C
- II 2G Ex db IIC Gb T5 Ta -50°C to +55°C
- II 2G Ex db IIC Gb T4 Ta -50°C to +70°C
- II 2D Ex tb IIIC Db T110°C Ta -50°C to +70°
|
Approval : |
-
IECEx UL 15.0003X
IEC 60079-0 : 2011
IEC 60079-1 : 2014
IEC 60079-31 : 2013
-
ATEX DEMKO 15ATEX1448X
EN 60079-0 : 2012
EN 60079-1 : 2014
EN 60079-31 : 2014
-
TR-CU Ex EAC certificate: RU C-GB.AA71.B.00109
|