Ordering Codes : |
|
Energy : |
10 Joules (10Ws) |
Flash Rate : |
1Hz (60 fpm) |
| Peak Candela : |
87,590 cd* - measured ref. to I.E.S. |
| Safety Integrity Level : |
Safety-integrity level: SIL2 |
| Inmetro Certificate : |
10-IEx-0010 |
| Eff Intensity Cd : |
250 cd - calculated from energy (J) |
| Peak Candela : |
1,000,000 cd - calculated from energy (J) |
| Eff Intensity Cd : |
120 cd* - measured ref. to I.E.S. |
| Lens Color : |
Amber, Blue, Clear, Green, Magenta, Red & Yellow |
| Voltage DC : |
12vdc; 24vdc; 48vdc |
| Voltage AC : |
115V ac; 230V ac |
| Ingress Protection : |
BG10D : IP66/67 BG10E : IP66 |
| Enclosure Material : |
Marine grade copper free LM6 Aluminium |
| Enclosure Finish : |
Chromate & powder coated finish - anti-corrosion. |
| Color : |
RAL3000 Red (others available on request) |
| Cable Entries : |
Dual M20 ISO (one stopping plug inc) |
| Terminals : |
0.5 - 2.5mm² (20-14 AWG) |
| Enclosure Volume : |
<2 litres |
| Line Monitor : |
Blocking diode included , EOL Min. 500 Ohm 2w, or 3k3 Ohm 0.5w resistor or diode (DC versions) can be fitted |
| Tube Life : |
Emissions are reduced to 70% after 5 million flashes |
| Grounding Stud : |
M5 |
| Temperature Range : |
-50° to +70°C (-58°F to +158°F) |
| Relative Humidity : |
95% - Additional tropicalisation is recommended for applications where both high relative humidity and high ambient temperatures exist |
| Weight : |
DC: 2.45kg/5.39Ibs AC: 2.75kg/6.05Ibs |
| Option S1 : |
SIL2 Compliant versions - contact E2S for technical info. |
Coding : |
- II 2G Ex d IIC T5 Gb Ta. -50°C to +45°C
- II 2G Ex d IIC T4 Gb Ta. -50°C to +70°C
- II 2D Ex tb IIIC T90°C Db Ta. -50°C to +40°C
- II 2D Ex tb IIIC T105°C Db Ta. -50°C to +55°C
- II 2D Ex tb IIIC T120°C Db Ta. -50°C to +70°C
|